ABB | SACE Emax 2
External electronic accessories
10 - Ekip Com Hub
241 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Interface
the module has three signaling leds:
1
2
Figure 137
LED Description
Power
Signals the on status and correct communication with Ekip Touch:
• Off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module
on and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
per second): module on and communication with Trip unit absent
Link (1)
Indicates the communication state:
• Off: incorrect connection, signal absent
• on fixed: correct connection
Activity (2)
Indicates the communication state:
• off: no activity on the line
• flashing (activity on line present receiving and/or transmitting)
Configurations via menu
Local bus activation, which is essential for starting the communication between module and Ekip Touch,
is available in the
Settings
menu (page 49).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the
Settings
-
Modules
menu:
Parameter Description Default
Enable
Switches communication between module and server on/off. Off
Static IP address ON
Defines whether the module has the dynamic (Off) or static
(On) IP address.
If = On all the associated parameters are enabled
Off
Static address IP
address
Enables the static IP to be selected 0.0.0.0
Static Network Mask
Enables the subnet mask to be selected 0.0.0.0
Static Gateway address
When there are several subnets, enables the IP address of the
node to which the module is connected to be selected
0.0.0.0
Enable SNTP client
Allows the SNTP protocol for distribution of the clock and
synchronization signal to be enabled.
Off
SNTP Server Addr.
Allows the network server that supplies the SNTP to be set. 0.0.0.0
Password
Code required to register module on Cloud ---