ABB | SACE Emax 2
Ekip Touch - Interface and menus
4 - Menu
50 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Installation menu
If Ekip Touch detects that
Rating Plug
or
Measurement
module have not been installed properly, it signals
an alarm (page 291) and completes
Settings
menu with the specific installation section:
Menu Submenus 1 Submenus 2 Commands
Circuit Breaker Installation
Rating Plug Install
Ekip Measuring Install
Correct installation is confirmed by a message on the display and disappearance of the alarm signal and
installation menu.
NOTE:
availability of submenus depends on the module, which appears to have not been
installed
Test Menu
Menu Submenus Description, parameters and Commands
Autotest
- Autotest command
Trip Test
- TRIP command
Test CB
-
Close CB
,
Open CB
Ekip Signalling 4K
(1)
- Module autotest command
Ekip Signalling 2K
(1)
Ekip Signalling 2K-1
(1)
Module autotest command
Ekip Signalling 2K-2
(1)
Ekip Signalling 2K-3
(1)
ZoneSelectivity
(2)
S Protection
(3)
Input
,
Force Output
,
Release Output
G Protection
(4)
Rc Test
(5)
- Test instructions
(1)
available if one or more Ekip Signalling modules are connected and detected by Ekip Touch
(2)
available if Ekip Touch is on with auxiliary supply
(3)
available with S and/or S2 and/or D protection enabled, for S protection the set curve must be t=k
(4)
available with G and/or D protection enabled and curve t=kavailable with G and/or Gext and/or
MDGF and/or D protection enabled and curve t=k
(5)
available if the Ekip CI module is connected and detected by Ekip Touch
About Menu
Menu Submenus Information provided
Protection Unit
-
Information about Ekip Touch: Trip unit serial
number, type, version, standard, SW version,
date and time, language
Protection Unit
-
Information about Ekip Touch: Mainboard serial
number, Trip unit serial number, type, version,
standard, SW version, date and time, language
Circuit Breaker
-
CB information: TAG name, CB name, rated
current, number of poles, CB status and
position, total operations, CB serial number
IEC 61557-12
(1)
-
Status of 1% measurements (from
Class 1 Power
& Energy Metering
package), serial number of
assembly and current sensors connected
Feature Collection
- List of tripped protections in Trip unit
Modules Modul x
(2)
Module information: serial number, SW version,
status of inputs/outputs/contacts (if present)
Power Controller
(3)
Load Input Status
Status of loads (open/closed)
Load Active
Load configuration (activated/not activated)
Load shedding
(3)
Load Input Status
Status of loads (open/closed)
Load Active
Load configuration (activated/not activated)
(1)
available if Class 1 Power & Energy Metering SW package is provided for by Trip unit module or if it
has been previously activated
(2)
available if one or more modules are connected and detected by unit

Table of Contents