Ekip Touch - Protections
2 - Standard Protections
56 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
L Protection
L
I1
t
t1
I
Function
If the current of one or more phases exceeds threshold I1, the protection trips and, after a time established
by the value read and by the parameter settings, transmits the TRIP command.
To check and simulate the trip times in relation to all the parameters, please consult:
the summary table of the protections with the calculation formulas (page 95)
the graph with trip curve (from page 98)
Parameters
Parameter Description Default
Curve
Establishes curve dynamics and trip time calculation:
• t = k / I
2
according to IEC 60947-2
• IEC 60255-151 SI
• IEC 60255-151 VI
• IEC 60255-151 EI
• t = k / I
4
according to 60255-151
t = k/I
2
Threshold I1
Establishes the value that activates the protection and
contributes towards calculating the trip time.
The value is given as both absolute value (A) and relative value (In)
and can be set within the range: 0.4 In to 1 In, in 0.001 In steps
1 In
Time t1
Contributes towards calculating the trip time.
The value is given in seconds and can be set within the range: 3 s
.. 144 s, in 1 s steps
144 s
Thermal
memory
Activates/deactivates the thermal memory function (page 83) OFF
Prealarm I1
Warns that the measured current is near to protection activation
threshold I1.
The value is given in percentage of threshold I1 and can be set
within the range: 50% I1 to 90% I1, in 1% steps.
NOTA: the prealarm condition deactivates in two cases:
• current lower than prealarm threshold I1
• current higher than threshold I1
90 % I1
Limitations and additional functions
threshold I1 must be lower than threshold I2 (if S protection is activated)
L protection: the trip time of the protection is forcibly set at 1 s if the calculation results give a
lower theoretical tt value and/or if the current reading is more than 12 In
with CB in UL standard configuration, the only available curve is t = k/I
2