Ekip Touch - Protections
6 - Power protections
76 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
D Protection
I7
t
t7fw
I
D
t7bw
Function
D protection is very similar to S protection, with the additional capability of recognizing the direction of
the current during a fault.
The current direction allows the user to find out whether the fault is on the supply side or load side of the
device controlled by Ekip Touch.
In ring type distribution systems, D protection allows the distribution section in which the fault has
occurred to be identified and disconnected without affecting the rest of the installation (using zone
selectivity).
Depending on the direction of the fault, if the current of one or more phases exceeds threshold I7 (I7fw or
I7bw) for longer than time t7 (t7fw or t7bw), the protection activates and sends a TRIP command.
The fault direction is established by comparing the detected fault current with the reference direction.
NOTE:
the reference direction is calculated considering the set value of the power flow
direction and the phase sequence (cyclic direction of the phases):
Phase sequence (set) Power flow (set)
Phase sequence (de
-
tected)
Reference direction
(forward direction)
123 High-->Low 123 High-->Low
123 Bottom --> Top 123 Bottom --> Top
123 High-->Low 321 Bottom --> Top
123 Bottom --> Top 321 High-->Low
321 High-->Low 123 Bottom --> Top
321 Bottom --> Top 123 High-->Low
321 High-->Low 321 High-->Low
321 Bottom --> Top 321 Bottom --> Top
To check and simulate the trip times in relation to all the parameters, please consult:
the summary table of the protections with the calculation formulas (page 95)
the graph with trip curve (page 109)
Parameter Description Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
ON
Threshold I7
Fw
Establishes the value that activates the protection with forward
direction.
The value is given as both absolute value (amperes) and relative value
(In) and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
2 In
Threshold i7
Bw
Establishes the value that activates the protection with backward
direction.
The value is given as both absolute value (amperes) and relative value
(In) and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
2 In
Time t7 Fw
This is the trip time in the case of forward direction.
The value is given in seconds and can be set within the range: 0.1 s to
0.8 s, in 0.01 s steps
0,2 s
Time t7 Bw
This is the trip time in the case of backward direction.
The value is given in seconds and can be set within the range: 0.1 s to
0.8 s, in 0.01 s steps
0,2 s
ZoneSelectivity
(1)
Activates/deactivates the function and selectivity time availability on
the display.
NOTE: configure selectivities S, S2, I, 2I, MCR and G OFF to ensure
that selectivity D functions correctly
NOTE: configure selectivities S, S2, I, 2I, MCR, G, Gext and
MDGF OFF to ensure that selectivity D functions correctly
OFF
Selectivity
time Fw
(1)
This is the trip time of the protection with the zone selectivity function
activated, forward direction and selectivity input Fw not present.
The value is given in seconds and can be set within the range: 0.1 s to
0.8 s, in 0.01 s steps
0,13 s
Selectivity
time Bw
(1)
This is the trip time of the protection with the zone selectivity function
activated, backward direction and selectivity input Bw not present.
The value is given in seconds and can be set within the range: 0.1 s to
0.8 s, in 0.01 s steps
0,13 s
Continued on the next page

Table of Contents