ABB | SACE Emax 2
Ekip Touch - Protections
9 - Additional protections and functions
90 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
RC Protection
Rc
Idn
t
I
tdn
Function
Rc protection protects against the residual current earth faults by detecting the fault current with the
appropriate external Rc toroid.
The protection sends a TRIP command if the current from toroid Rc exceeds threshold Idn for longer than
Tdn.
To check and simulate the trip times in relation to all the parameters, please consult:
summary table of the protections with the operating characteristics (page 95)
the graph with trip curve (page 103)
Parameters
Parameter Description Default
Threshold Idn
Defines the value that activates the protection; the value is given
in amperes and can be set within a range of values from 3 A to 30
A
3 A
Time Tdn
This is the trip time of the protection; the value is given in
seconds and can be set within a range of values from 0.05 s to
0.8 s
0,06 s
Limitations and additional functions
Ekip Touch activates and displays the Rc protection parameters if the following conditions are observed:
Rating Plug
Rc model assembled and installed
Measurement
module assembled and installed
protection activation includes checking for the presence of toroid Rc and signaling on the diagnosis bar
in the event of alarm/absence