EasyManua.ls Logo

ABB SACE Emax E4.2 - Page 154

ABB SACE Emax E4.2
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
Mechanical characteristics
1 - E1.2 description
151 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Manual operations for opening
and closing the circuit-breaker
The following is the sequence of steps for closing and opening the circuit-breaker:
1. Check that the circuit-breaker is open (open / closed indicator "O - OPEN"), and check that the
springs are discharged (spring signalling device "white - DISCHARGED SPRING") as indicated in
Figure 42.
2. Charging the springs - Pull the lever [A] downwards several times until the springs charged
signalling device [B] is “yellow - CHARGED SPRING” as indicated in Figure 43.
Figure 42
A
B
Figure 43
3. Check that the circuit-breaker is open (open/closed signalling device “O - OPEN”), and check that
the springs are charged (springs signalling device “yellow - CHARGED SPRING”) as indicated in
Figure 44.
4. Closing - Press the closing pushbutton “I - Push ON” as indicated in Figure 45.
Figure 44
Figure 45
5. Check that the circuit-breaker is closed (open/closed indicator "I - CLOSED"), and check that the
springs are discharged (spring signalling device "white - DISCHARGED SPRING" as indicated in
Figure 46.
6. Opening - Press the opening pushbutton “O - Push OFF” as indicated in Figure 47.
Figure 46
Figure 47
Continued on the next page

Table of Contents

Other manuals for ABB SACE Emax E4.2

Related product manuals