1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 | 118
Enabling and fields to edit the Clients page (5 information lines) that can be viewed from the unit
display.
The counter indicates the elapsed time since the last reset of the energy measurements.
It is active and updated if there is either an auxiliary power supply or a power supply from Ekip
T&P.
The parameter allows changing the behavior of the Trip unit's Power LED and all connected
modules. If activated (Alive Mode on), the Power LEDs behave as follows:
Ekip Touch: flashes with 0.5 Hz frequency
Modules: if there are no communication errors, they synchronize with the Ekip Touch LED
If deactivated, the Power LEDs on the respective devices are on and fixed.
Open/Close
Remote Direct
Command
The parameter manages two different command packages for remote opening and closing:
Enabled: direct Open and Close commands are valid.
Disabled: direct commands not valid. In this case, remote opening and closing are possible
using the YC COMMAND and YO COMMAND programmable functions and the commands
Request circuit breaker open and Request circuit breaker close.
Change Dual
Setting of
parameters
always
If activated, it allows changing the parameter settings (Adaptive Protections) also with timing
alarms in progress.
Disabled by default.
Repeat zone
selectivity S/G
HW
If Enabled, the propagation logic of the zone selectivity HW signals is valid according to the table
in the technical notebook QT1 1SDC007100G0205.
If Disabled, the HW selectivity signal is not propagated by Ekip Touch
Zone selectivity
input functions
In this section it is possible to configure the zone selectivity inputs and some outputs:
Standard: operation of the input or output as per standard zone selectivity logic (see
1SDC007100G0205 or 1SDC007401G0201). All the selectivity functions are set with
Standard.
Custom: it is possible to select the activation event of the zone selectivity input or output.
IMPORTANT: in the Custom configuration the only event to activate zone
selectivity is the one set, and therefore the standard selectivity operation is not
active (change recommended only for expert technical staff)
The Glitch commands from 16 to 23 activate the respective glitch registers, useful for customizing
any programmable functions or output contacts.