13 - Password and security
Function
The password is intended to prevent unintentionally setting incorrect parameters
from the display.
However, changing parameters without entering the password is allowed from:
Service connector, with Ekip T&P or Ekip Programming and the Ekip Connect application
Bus, with Ekip Com modules and with the Trip unit configured Remote (page 29)
WARNING! it is suggested to set a password for the Ekip Connect and the remote
control system
Safety
WARNING! it is the user's responsibility to configure the security to prevent
unauthorized accesses and changes
Description
The password is a five-digit number, each of which can have a value from 0 to 9. The default
value is: 00001.
The password is required when:
Selecting a parameter to be changed (including the password itself, in the Settings menu)
Selecting the Test menu
Entering the password allows access to all menus without having to re-enter it repeatedly if the
operations are carried out within a time of two minutes. Once this time has elapsed it must be
entered again, where necessary.
NOTE: the password also expires when a programming session is canceled (page 31)
Entering the
password
To enter the password it is necessary to confirm each digit using the Enter button, changing the
digit as needed with the Right/Up and Left/Down buttons. To confirm the entry of the password
it is therefore necessary to press Enter five times:
Figure 18
Disabling the
password
You can disable the password by setting it to the value: 00000.
In this situation the only action that will require entering the password is changing the password
itself, in the Settings menu.
Exceptions
NOTES:
If the wrong password is entered, the message "Password incorrect" will appear
for about 3 seconds and the page for entering the password will re-open
There is no limit to the number of incorrect passwords that can be entered
If the password is lost, see the document 1SDH001501R0001 available on the
ABB website, or contact ABB directly