EasyManua.ls Logo

ABB SACE Tmax XT2 - Load Shedding

ABB SACE Tmax XT2
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 122
35 - Load Shedding
Description
The Load Shedding function allows you to manage malfunctions on systems that can work thanks
to the energy produced by renewable and local energy sources, in particular a lack of power,
e.g. due to a malfunction on the MV voltage side.
The function is available in two versions:
Basic is supplied with all Ekip Touch Trip units
Adaptive can be purchased with the relative additional package that is available for all
Trip units equipped with the Measuring Measurement package, excluding Ekip M Touch
All the parameters and measurements of the function are available via Ekip Connect, while the
Trip unit allows setting and viewing some of them, as noted below.
Ekip Touch
Parameters
Some function configuration parameters are available In the Settings - Load Shedding menu
(page 29).
NOTE: it is advisable to first configure the parameters via Ekip Connect, and only then
operate on the Trip unit
Parameter
Description
Default
Enable
Enable/disable the function and the availability of the parameters in
the menu
OFF
Version
Display of the function version, Basic or Adaptive
E
NOTE: with the Basic version the only parameter available
is Reconnection Timeout
--
Solar System
Present
Defines if the microgrid includes a solar system (Off/On)
Off
Solar rated power
Available with Solar System Present = On, defines the rated power of
your solar system.
The value is expressed in kW, which can be set in a range:
100 kW .. 65535 kW with 1 kW steps
100 kW
ATS
Defines if the system has an ATS system (Off/On)
Off
Generator power
Available with ATS = On, it defines the power received from the ATS
branch, which can be set in a range:
0 kW (. . . .) .. 10000 kW with 1 kW steps
. . . .
Frequency slope
(NOTE)
Defines the variation of real-time frequency that triggers Load
shedding
The value is expressed in (Hz/s), which can be set in a range:
0.6 Hz/s .. 10 Hz/s with 0.2 Hz/s steps
0.6 Hz/s
FW Warning
(NOTE)
Minimum frequency control threshold that activates Load shedding
The value is expressed in an absolute value (Hertz), which can be set
in a range: 0.9 Fn .. 1.1 Fn with 0.001 Fn steps
1 Fn
Reconnection
Timeout
Defines the time used by the Trip unit between the one load and the
next, following the re-closure of the main CB.
The value is expressed in (s), which can be set in a range:
10 s ..1800 s with 1 s steps
10 s
NOTE: Load shedding is activated if the control conditions defined by the Frequency
slope and FW Warning parameters are simultaneously present

Table of Contents

Other manuals for ABB SACE Tmax XT2

Related product manuals