1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 131
40 - Ekip Com Modbus RTU
Ekip Com Modbus RTU is a communication accessory that enables Ekip Touch to be integrated
into a RS-485 network with Modbus RTU communication protocol, with remote supervision and
control functions, in two different modes, master and slave.
From remote it is possible to:
read information and Ekip Touch measurements
manage certain commands, including opening and closing actuator (MOE-E)
access to information and parameters that are not available on the display
if connected to a withdrawable circuit-breaker, check the status of inserted / extracted
NOTE: the remote open and close commands to the switch can be run only if Ekip
Touch is in Remote configuration
To map the module in its own communication network, the document System Interface is
available (page 128), in which all the necessary communication and command details are listed.
To connect Ekip Modbus RTU to Ekip Touch, the Ekip Cartridge (page 129) and Ekip Supply
(page 130) accessories are required.
Models
Ekip Touch can be configured with two different modules that are compatible with the Modbus
RTU protocol: Ekip Com Modbus RTU and Ekip Com Modbus RTU Redundant.
The two modules are identical in terms of characteristics and installation methods, except for:
display menus on unit, cablings and addresses for external communication, that are specific for
each model.
NOTE: if not specified, the information in the following chapter applies to both models
Both modules can be connected simultaneously to Ekip Touch to increase the potential of unit
(for example: for applications in which great network reliability is necessary).
Connections
Consult:
the electrical diagrams for 1SDM000068R0001 to connect the module to its
communication network and for terminal references.
The connections must be made with Belden 3105A or equivalent cables.
the instruction sheets 1SDH002009A1503 to connect the module to Ekip Supply and
Ekip Touch.
Supply
Ekip Com Modbus RTU is supplied directly by the Ekip Supply module to which it is connected.
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted