1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 183
54 - Ekip Com Modbus TCP
Ekip Com Modbus TCP is a communication accessory that enables Ekip Touch to be integrated
into an Ethernet network with Modbus TCP communication protocol, with remote supervision and
control functions, in two different modes, standard and HTTP server.
The module is configured as master and from remote it is possible to
read Ekip Touch information and measurements
manage certain commands, including opening and closing actuator (MOE-E)
access information and parameters that are not available on the display
NOTE: the remote open and close commands to the switch can be run only if Ekip
Touch is in Remote configuration
To map the module in its communication network, the document System Interface is available
(page 128) that lists the necessary communication and command details.
Depending on the parameters set, which are illustrated on subsequent pages, the following
module ports are used:
Port
Service
Notes
502/tcp
TCP Modbus
Valid for TCP Modbus modes
80/tcp
Server HTTP
Valid for Server HTTP modes
319/udp
IEEE 1588
Valid with IEEE 1588 protocol enabled
320/udp
68/udp
DHCP client
DHCP client enables alternatively to: static address = On
Safety
As the module enables the actuator to be controlled that is connected to Ekip Touch and enables
unit data to be accessed, it can be connected only to networks meeting all the necessary security
and unauthorized-access prevention requirements (e.g. the control system network of a plant).