1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 182
Configurations
Resistances can be linked to bus RS-485, configuring dip switches located on the side of the
module:
Figure 47
Resistances
Dip switch
Description
Default
Rterm
1 and 2
Termination resistance 120
Move dip switches 1 and 2 to ON position to
connect Rterm
Off
Menu
Activating the local bus is required to start communication between the module and Ekip Touch
and is available in the Settings menu (page 114).
If the module is detected correctly by Ekip Touch two areas are activated:
information area in the About-Modules menu containing the software version and the serial
number of the module
area of specific configuration in the Modules Settings menu, in which the following
communication parameters can be configured:
Parameter
Description
Default
Serial
address
Module address; range from 1 to 247 available
IMPORTANT: devices connected to the same
network must have different directions
247
/
246
(NOTE)
Baudrate
Data transmission speeds: 3 options available:
9600 bit/s, 19200 bit/s, 38400 bit/s
19200 bit/s
Physical
protocol
Define the stop and parity bit; 4 options available:
8,E,1 = 8 bit datum,1 EVEN parity bit, 1 STOP bit
8,O,1 = 8 bit datum, 1 ODD parity bit, 1 STOP bit
8,N,2 = 8 bit datum, no parity bit, 2 STOP bits
8,N,1 = 8 bit datum, no parity bit, 1 STOP bit
8,E,1
NOTE: 247 default of the module Ekip Com Modbus RTU
Remote
information
From the service connector (via Ekip Connect) or with a system bus communication, additional
information is available on the version and the status of the module: HW and Boot version, CRC
status (correctness of SW in the module).