1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 | 70
22 - Additional functions and protections
Some protections are provided with additional functions that extend their characteristics and
performance:
Overheating of the cables
Management of TRIPs in a network of switches
Protection block according to programmable events
Different thresholds according to control thresholds
The presence of Ekip Synchrocheck allows the activating of the module protections (see details
at page 74):
The function, which can be activated for the L and S protections, prevents the overheating of
cables connected to the device controlled by Ekip Touch. In the case of multiple opening
commands in a short period of time the unit considers the time elapsed between the commands
and the magnitude of the malfunctions to reduce the trip time.
NOTE: the function changes the trip time even in the event of overloads that do not
lead to the opening command
Zone selectivity
S, S2, and G
Preface
The function, which can be activated for the S, S2 and G protections (if available and enabled),
allows connecting several devices belonging to the same system, including Ekip Touch, to better
manage the trip commands in case of S, S2 e G protections.
The function allows coordinating the devices so that in the event of a malfunction:
The device closest to the malfunction is triggered
The other devices are blocked for a programmable time
NOTE: the connection is possible between ABB devices that have the zone selectivity
function
Characteristics
Ekip Touch has five selectivity links:
Protections S and S2 selectivity input
Protections S and S2 selectivity output
Protections G selectivity input
Protections G selectivity output
Municipality of selectivity network
The entire selectivity
network