1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 97
Events
Ekip Touch can log the last 200 events, mainly related to changes in status and operation of the
unit, specifically:
Status of the bus configuration, operating mode, active setting, auxiliary power supply
States or connection alarms: Current sensors, Trip Coil
Protections: timing in progress or alarm
Trip: status of the opening command, trip signal
NOTE: in the log the first entry is the most recent. Once the 200-event threshold is
exceeded, the oldest ones are progressively overwritten
The complete list is available in the Measurements - Log - Events menu, where each event is
accompanied by a series of information: icon representing the type of event, event name, and
event date and time.
There are four icons that identify the type of event:
Icon
Description
Event reported for informational purposes
Timing of a protection in progress, trip pending
Alarm referring to a non-dangerous condition
Operating alarm, malfunction, or connection error
Openings
Ekip Touch is able to log the last 30 TRIPs.
The complete list is available in the Measurements - Log - Openings menu, where each trip
includes the following useful information:
The protection that triggered the opening
The progressive count of the opening
The date and time of the opening (referring to the internal clock)
The measurements associated with the protection that was triggered
NOTE: if the 30-TRIP threshold is exceeded, the oldest events are progressively
overwritten
Related measurements
The protection that trips determines the measurements recorded at the time of opening:
Protection
Measurements
recorded
Remarks
Power
Currents L1, L2, L3,
Ne, Ig
Ne is available with CB 4P and 3P + N
Ig is available in the event of trips for G protection
Temperature
Currents L1, L2, L3, Ne
The temperature cannot be seen on the display