1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 | 136
Activating the local bus is required to start communication between the module and Ekip Touch
and is available in the Settings menu (page 114).
If the module is detected correctly by Ekip Touch two areas are activated:
information area in the About-Modules menu containing the software version and the serial
number of the module
area of specific configuration in the Modules Settings menu, in which the following
communication parameters can be configured:
Module address; range from 1 to 125 available
IMPORTANT: devices connected to the same
network must have different directions
NOTE: 125 default of the module Ekip Com Profibus DP; 124 default of the module
Ekip Com Profibus DP Redundant
From the service connector (via Ekip Connect) or with a system bus communication, additional
information is available on the version and the status of the module: HW and Boot version, CRC
status (correctness of SW in the module).