EasyManua.ls Logo

ABB SACE Tmax XT2 - Page 158

ABB SACE Tmax XT2
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 158
Configurations
on menu
Activating the local bus is required to start communication between the module and Ekip Touch
and is available in the Settings menu (page 128).
If the module is detected correctly by Ekip Touch, in the Settings Modules menu, the following
communication parameters can be configured:
Parameter
Description
Default
Static IP address ON
Defines whether the module has the dynamic IP address
(Off) or static IP address (On); if = On all the associated
parameters are enabled
Off
Static IP address
Enables the static IP to be selected
0.0.0.0
Static Network Mask
Enables the subnet mask to be selected
0.0.0.0
Static Gateway
address
In the presence of several subnets it enables the IP address
to be selected of the node to which the module is connected
0.0.0.0
Information on
menu
If the module is detected correctly by Ekip Touch in the About-Modules menu the following
information is available:
Information
Description
SN and version
Identification and SW version of the module
IP address
Address of the module, assigned to the module by a DHCP server at the
moment of connection to the network in the event of configuration with dynamic
or settable IP that can be set by the menu in the event of a static IP
NOTE: without a DHCP server, the module automatically adopts a
causal IP address in the interval 169.254.xxx.xxx
Network Mask
Subnet mask; identifies the method for recognizing the subnet to which the
modules belong and enables modules to be searched for within a defined set of
recipients
Gateway address
IP address of the node to which the module is connected, in the presence of
several subnets
MAC Address
Address assigned by ABB with OUI (Organizationally Unique Identifier) equal to
ac:d3:64 that identifies uniquely the manufacturer of an Ethernet device