1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 – XT4 | 198
If the module is correctly detected by Ekip Touch, the following information is available in the
Information-Modules menu:
Module identifier and SW version
Module address, assigned to the module by a DHCP server when connecting to
the network with a dynamic IP, or settable from the menu when using a static IP
NOTE: without a DHCP server, the module automatically adopts a
random IP address in the range 169.254.xxx.xxx
Identifies the method for recognizing the subnet to which modules belong, with
the possibility of searching for modules within a set of defined recipients
IP address of the node to which the module is connected when there are multiple
subnets
Address assigned by ABB with OUI (Organizationally Unique Identifier) equal to
ac:d3:64 that uniquely identifies the manufacturer of an Ethernet device
From the service connector (via Ekip Connect) or with system bus communication it is also
possible to access additional parameters.
Parameter to change the module configuration from Server Only to
Client and Server and integrate it into an interactive data exchange
network (see Ekip Com Hub on page 156)
IMPORTANT: if Client/Server, the module allows
data exchange as per normal Server operations
Enable the IEEE 1588 protocol for clock signal distribution and
synchronization
(1)
Set the module as a master in the network segment it belongs to
(synchronization clock)
IEEE 1588 delay
mechanism
Choose the mode of data exchange between module and master,
either Peer-to-Peer or End-to-End
Enable the SNTP protocol for clock signal distribution and
synchronization
(1)
Identify the network server that provides SNTP
Defines the time zone to be used for synchronization
Specifies whether the local country uses daylight saving time (ON)
or not (OFF)
Enable (ARP Enabled) the periodic generation of a Gratuitous ARP
message, used by Ekip Connect to quickly find the modules with an
Ethernet scan without knowing the IP address in advance
Password protected
access
Protect the write operations carried out from the network with a
password (password required)
With password-protected access enabled, it is the password to be
used before each write session
(2)
NOTES:
(3) IEEE 1558 and SNTP client must not be enabled at the same time
(4) the parameter can only be changed via system bus in remote configuration