Function
If the current of one or more phases exceeds the I1 threshold, the protection is activated and,
after a time determined by the value read and the parameters set, it sends the TRIP command.
To verify and simulate the trip times based on all the parameters, see:
Protection summary table with the formulas for calculations (page 78)
Chart with tripping curve (pages 81, 82, 83)
Parameters
NOTE: the Ekip M Touch Trip unit has default constraints and parameters that are
different from the other models. The details are shown after the table.
Determines curve dynamic and calculation of trip time:
t=k/I
2
in accordance with IEC 60947-2
IEC 60255-151 SI
IEC 60255-151 VI
IEC 60255-151 EI
t=k/I
4
in accordance with 60255-151
Defines the value that activates protection and contributes to
calculating trip time.
The value is expressed both as an absolute value (Ampere) and
as a relative value (In), settable in a range:
0.4 In .. 1In with 0.001 In step.
Contributes to calculating trip time.
The value is expressed in seconds, which are settable in a range:
3 s .. 60 s, with 1 s step.
Activates/deactivates the thermal memory function, see page 70
for details
NOTE: the function is always ON with Ekip M Touch trip
unit and available for all the others Trip unit model with a
curve t=k/I
2
Enables a warning to be sent that the measured current is near
the threshold triggering the protection.
The value is expressed as a percentage of the threshold I1, which
is settable in a range: 50 % I1 .. 90 % I1, with 1 % step.
The pre-alarm threshold is deactivated in two cases:
current below pre-alarm threshold I1
current above threshold I1
Ekip M Touch
L protection of the Ekip M Touch differs with the other models in the following ways:
Curve: cannot be changed and is specific for Ekip M Touch (see page 84)
Time t1: cannot be changed and is determined by the trip class (see page 66)
Thermal memory: always enabled, operating according to IEC 60255-8; thermal memory
reset time set by the trip class (see page 66)
Different default parameters: I1 = 0.4 In; t1 = 45 s (Class = 20E)
Constraints, limitations, and additional functions
The I1 threshold must be less than the I2 threshold (if the S protection is active)
The protection trip time is forced to 1 s if the calculations result in a lower theoretical value
and/or if the current detected is higher than 12 In