EasyManua.ls Logo

ABB SACE Tmax XT2 - Page 53

ABB SACE Tmax XT2
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1SDH002031A1002 ECN000092998 Rev. B SACE Tmax XT2 XT4 | 53
S2(V) Protection
[2]
Parameter
Description
Default
Threshold
Uh2
The parameter is shown with a Lin curve and helps to calculate the trip
threshold I21:
Mod
Voltage read
Trip threshold
Lin
< Uh2 (and Ul2)
The threshold varies gradually (see
above)
Uh2
I21
The value is expressed both as an absolute value (Volt) and as a relative
value (Un), settable in a range: 0.2 Un .. 1 Un with 0.01 Un step
1 Un
Threshold
Ks2
Threshold I21 calculation constant.
The value is expressed as a percentage value of the threshold I21, which
is settable in a range: 0.1 I20 .. 1 I20 with 0.01 step
0.6 I20
Time t21
This is the trip time of the protection.
The value is expressed in seconds, which are settable in a range:
0.05 s ..30 s, with 0.01 s step
0.1 s
Constraints, limitations, and additional functions
From the service connector (with Ekip Connect) or with system bus communication it is also
possible to access the block functions, see page70.
RV Protection
Function
The protection is activated in case of loss of insulation (check residual voltage U0). If the voltage
U0 exceeds the threshold U22 for a time greater than t2, the protection sends the TRIP
command.
The protection is always available in 4P configuration.
To verify and simulate the trip times based on all the parameters, see:
Protection summary table with the operating characteristics (page 79)
Chart with tripping curve (page 89)
Parameters
Parameter
Description
Default
Enable
Enables/disables protection and availability on menu of the
parameters
OFF
Trip Enable
Activates/deactivates the open command: if disabled, the alarm
and the lapsing of the protection time are managed only as
information
OFF
Threshold
U22
Defines the value that activates the protection.
The value is expressed both as an absolute value (Volt) and as a
relative value (Un), settable in a range:
0.05 Un .. 0.5 Un with 0.001 Un step
0.15 Un
Time t22
This is the trip time of the protection; the value is expressed in
seconds, which are settable in a range:
0.05 s .. 120 s, with 0.01 s step
15 s
Reset Time
This is the alarm maintenance time after the protection has left the
alarm condition; this can be useful for keeping the timing active
even in the presence of temporary deactivation of the protection.
The value is expressed in seconds, settable in a range:
0 s .. 0.2 s, with 0.02 s step
0 s
Constraints, limitations, and additional functions
From the service connector (with Ekip Connect) or with system bus communication it is also
possible to access the block functions, see page70.

Table of Contents

Other manuals for ABB SACE Tmax XT2

Related product manuals