4.3.5 Addressing Lon-Bus
29 words, each with 16 bits, are transmitted. The addressing is as follows:
Add-
ress
Content Word type
Direction
of trans-
mission
Format
Scaling
Signal name
1 Digital inputs Bit-coded
read*
--
--
NV_Syn5_inputs_out
2 Digital outputs Bit-coded
read
--
--
NV_Syn5_output1
3 Digital outputs Bit-coded
read
--
--
NV_Syn5_output2
4
Actual value U
nalog val.
read
signed integer**
0.1 % of Un
NV_Syn5_delta_U
5
Actual value
nalog val.
read
signed integer
0.1 DEG
NV_Syn5_alpha
6
ctual value s
nalog val.
read
signed integer
0.01 %
NV_Syn5_slip
7
ctual value U1
nalog val.
read
signed integer
0.1 % of Un
NV_Syn5_U1
8
ctual value U2
nalog val.
read
signed integer
0.1 % of Un
NV_Syn5_U2
9
ctual value f1
nalog val.
read
signed integer
0.01 Hz
NV_Syn5_f1
10
ctual value f2
nalog val.
read
signed integer
0.01 Hz
NV_Syn5_f2
11
ctual value ds/dt
nalog val.
read
signed integer
0.01 %/s
NV_Syn5_ds_dt
12 Back-indication of selected
parameter set
nalog val.
read
unsigned integer ***
Number of the
selected parameter set
NV_Syn5_Parameterset
13 Software version
nalog val.
read
unsigned integer
One digit of the version
number per nibble (half
byte)
(e.g.: 5137d = 1411h =
V1.4.1.1)
NV_Syn5_SW_version
14 Command counter reading par-set 1
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close1
15 Command counter reading par-set 2
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close2
16 Command counter reading par-set 3
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close3
17 Command counter reading par-set 4
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close4
18 Command counter reading par-set 5
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close5
19 Command counter reading par-set 6
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close6
20 Command counter reading par-set 7
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close7
21 Current event (event code)
nalog val.
read
unsigned integer
none
NV_Syn5_event_code
22 Year of the current event
nalog val.
read
unsigned integer
none
NV_Syn5_event_year
23 Month of the current event
nalog val.
read
unsigned integer
none
NV_Syn5_event_month
24 Day of the current event
nalog val.
read
unsigned integer
none
NV_Syn5_event_day
25 Hour of the current event
nalog val.
read
unsigned integer
none
NV_Syn5_event_hour
26 Minute of the current event
nalog val.
read
unsigned integer
none
NV_Syn5_event_minute
27 Second of the current event
nalog val.
read
unsigned integer
none
NV_Syn5_event_second
28 Hundredth of a second of the current
event
nalog val.
read
unsigned integer
none
NV_Syn5_one_hundredth
29 Digital inputs Bit-coded
write
--
--
NV_Syn5_inputs
* read = read data from SYNCHROTACT 5
** signed integer = whole numbers
*** unsigned integer = positive whole numbers