EasyManua.ls Logo

ABB SYNCHROTACT 5 - Actual Value U; Digital Input

ABB SYNCHROTACT 5
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating Instructions SYN 5201/SYN 5202
Document No Art Part Language Revision page
abb
ABB Switzerland Ltd
3BHS109762 E01
en D 56
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
4.3.5 Addressing Lon-Bus
29 words, each with 16 bits, are transmitted. The addressing is as follows:
Add-
ress
Content Word type
Direction
of trans-
mission
Format
Scaling
Signal name
1 Digital inputs Bit-coded
read*
--
--
NV_Syn5_inputs_out
2 Digital outputs Bit-coded
read
--
--
NV_Syn5_output1
3 Digital outputs Bit-coded
read
--
--
NV_Syn5_output2
4
Actual value U
A
nalog val.
read
signed integer**
0.1 % of Un
NV_Syn5_delta_U
5
Actual value
A
nalog val.
read
signed integer
0.1 DEG
NV_Syn5_alpha
6
A
ctual value s
A
nalog val.
read
signed integer
0.01 %
NV_Syn5_slip
7
A
ctual value U1
A
nalog val.
read
signed integer
0.1 % of Un
NV_Syn5_U1
8
A
ctual value U2
A
nalog val.
read
signed integer
0.1 % of Un
NV_Syn5_U2
9
A
ctual value f1
A
nalog val.
read
signed integer
0.01 Hz
NV_Syn5_f1
10
A
ctual value f2
A
nalog val.
read
signed integer
0.01 Hz
NV_Syn5_f2
11
A
ctual value ds/dt
A
nalog val.
read
signed integer
0.01 %/s
NV_Syn5_ds_dt
12 Back-indication of selected
parameter set
A
nalog val.
read
unsigned integer ***
Number of the
selected parameter set
NV_Syn5_Parameterset
13 Software version
A
nalog val.
read
unsigned integer
One digit of the version
number per nibble (half
byte)
(e.g.: 5137d = 1411h =
V1.4.1.1)
NV_Syn5_SW_version
14 Command counter reading par-set 1
A
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close1
15 Command counter reading par-set 2
A
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close2
16 Command counter reading par-set 3
A
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close3
17 Command counter reading par-set 4
A
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close4
18 Command counter reading par-set 5
A
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close5
19 Command counter reading par-set 6
A
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close6
20 Command counter reading par-set 7
A
nalog val.
read
unsigned integer
none (0 to 65535) NV_Syn5_close7
21 Current event (event code)
A
nalog val.
read
unsigned integer
none
NV_Syn5_event_code
22 Year of the current event
A
nalog val.
read
unsigned integer
none
NV_Syn5_event_year
23 Month of the current event
A
nalog val.
read
unsigned integer
none
NV_Syn5_event_month
24 Day of the current event
A
nalog val.
read
unsigned integer
none
NV_Syn5_event_day
25 Hour of the current event
A
nalog val.
read
unsigned integer
none
NV_Syn5_event_hour
26 Minute of the current event
A
nalog val.
read
unsigned integer
none
NV_Syn5_event_minute
27 Second of the current event
A
nalog val.
read
unsigned integer
none
NV_Syn5_event_second
28 Hundredth of a second of the current
event
A
nalog val.
read
unsigned integer
none
NV_Syn5_one_hundredth
29 Digital inputs Bit-coded
write
--
--
NV_Syn5_inputs
* read = read data from SYNCHROTACT 5
** signed integer = whole numbers
*** unsigned integer = positive whole numbers

Related product manuals