Electrical connection   
18 TTR200 OI/TTR200-EN 
 
Pos: 14.16 /Überschri ften/1.1/1-spa ltig/D - F/Elektrisc he Zusammenschaltung i m explosionsgefährdet en Bereich @ 16\mod_119815433 9484_3101.doc @ 146654 
 
5.5  Electrical interconnection in explosion risk area 
 
Pos: 14.17 /Elektri scher Anschluss/Temper atur/TTR200/Elek trische Zusammenscha ltung im explosionsgesc hützten Bereich @  16\mod_1198162640515_310 1.doc @ 146700 
 
Special interconnections are required for use in hazardous areas depending on the safety 
requirements. 
Intrinsic safety  
The Power supply SPS inputs must have corresponding input protection circuits available in 
order to eliminate a hazard (spark formation). An interconnection inspection must be performed. 
For proof of the intrinsic safety, the electrical limit values are to be used as the basis for the 
prototype test certificates of the apparatuses (devices), including capacitance and inductivity 
values of the wires. The proof of the intrinsic safety is given if the following conditions are 
fulfilled with comparison of the limit values of the apparatus. 
 
Transmitter 
(intrinsically safe apparatus) 
Power supply / SPS input 
(related apparatus) 
U
i
 
 
U
o
 
I
i
 
 
I
o
 
P
i
 
 
P
o
 
L
i
 + L
c
 (cable) 
 
L
o
 
C
i
 + C
c
 (cable) 
 
C
o
 
 
Field (Ex area)  Control room (secure area) 
 
Fig. 7 
 
A Transmitter 
 
B  Power supply SPS input 
 
 
Important 
Observe the “Technical specifications” and “Explosion-protection technical data” chapters (see 
data sheet and/or operating instructions). 
 