Technical data
OI/TTR200-EN TTR200 33
Pos: 27 /==== Wechsel zwei- auf einspaltig === = @ 0\mod_1130421955859_310 1.doc @ 3829
Change from one to two colu mns
Pos: 28.1 /Überschri ften/1/S - U/Technische D aten @ 0\mod_113290457 4837_3101.doc @ 3169
12 Technical data
Pos: 28.2 /==== Wec hsel ein- auf zweispaltig === = @ 0\mod_1130421847171_3101. doc @ 3828
Change from one to two colu mns
Pos: 28.3 /Überschri ften/1.1/2-spa ltig/D - F/Eingang @ 0\mod_1139 395051468_3101.doc @ 3221
12.1 Input
Pos: 28.4 /Technische Dat en / Datenblatt/ Temperatur/TTR/Techni sche Daten/Eingang @ 15\mod_ 1194864822515_3101. doc @ 139745
12.1.1 Resistance
RTD resistance thermometer
Pt100 in acc. with DIN IEC 60751, JIS, MIL, Ni in acc. with
DIN 43760, Cu
(for additional information, see the section "Measuring accuracy")
Resistance measurement
0 … 500
0 … 5000
Sensor connections
2-, 3-, 4-wire circuit
Connecting cables
2-, 3-, 4-wire max. sensor line resistance (R
W
) for each wire 50 Ω
in acc. with NE 89 (March 2003);
(3-wire balanced, 2-wire circuit compensation up to 100 Ω sensor
total line resistance)
Measurement current
< 300 µA
Sensor short-circuit
< 5 Ω (for RTD)
Sensor wire break (temperature resistance measurement 2-, 3-,
4-wire)
Measuring range 0 ... 500 Ω > 0.6 ... 10 kΩ
Measuring range 0 ... 5 kΩ > 5.3 ... 10 kΩ
Corrosion detection in accordance with NAMUR NE 89
3-wire resistance reading > 50 Ω
4-wire resistance reading > 50 Ω
12.1.2 Thermocouples/Voltages
Types
B, E, J, K, L, N, R, S, T, U, C, D
Voltages
-125 ... 125 mV
-125 ... 1100 mV
Connecting cables
Max. sensor line resistance (R
W
) for each line 1.5 kΩ, total 3 kΩ
Sensor wire break monitoring in accordance with Namur NE 89
pulsed with 1 µA outside the measurement interval
Thermocouple measurement 5.3 ... 10 kΩ
Voltage measurement 5.3 ... 10 kΩ
Input resistance
> 10 MΩ
Internal reference junction
Pt1000, DIN IEC 60751 Cl. B
(no jumpers necessary)
Sensor matching
via single point (offset adjustment)
via two point adjustment
Sensor fault signaling
RTD sensor: Short circuit and wire break
Linear resistance measurement: Wire break
Thermocouple: Wire break
Linear voltage measurement: Wire break
Pos: 28.5 /====== = Spaltenumbruch ======= = @ 0\mod_1132937966324_3101.d oc @ 3831
Pos: 28.6 /Technische Dat en / Datenblatt/ Temperatur/TTH/Techni sche Daten/Ausgang @ 0\mod _1139219931451_3101.d oc @ 3765
12.2 Output
Transmission characteristics
temperature linear
resistance linear
voltage linear
Output signal
Configurable 4 ... 20 mA (standard)
Configurable 20 ... 4 mA
(NE43 dynamic range: 3.8 ... 20.5 mA)
Simulation mode
3.5 ... 23.6 mA
Induced current consumption
< 3.5 mA
Maximum output current
23.6 mA
Configurable error current signal
override 22 mA (20.0 … 23.6 mA)
underdrive 3.6 mA (3.5 … 4.0 mA)
Pos: 28.7 /====== = Seitenumbruch ======= = @ 0\mod_1126532365768_3101.doc @ 3830