6 Startup Operation
Pos: 17 /Hinweise/W ichtig/Wichtig - Inbetriebnahme (Werksei nstellung) @ 18\mod_12051 57041951_3101.doc @ 168788
Important
The transmitter is immediately ready for operation after mounting and installation of the
connections. The parameters are set at the factory.
The connected wires must be checked for firm seating. Only firmly seated wires ensure full
functionality.
Pos: 18 /==== Leeres Modul mit einer Absatzmarke, IM, 1-spaltig ==== @ 14\mod_1 194422545687_0.doc @ 136717
Pos: 19.1 /Überschri ften/1/J - L/Kommunika tion und Konfiguration @ 1\ mod_1144747059078_31 01.doc @ 6033
K
7 Communication and configuration
Pos: 19.2 /Überschri ften/1.1/1-spa ltig/J - L/Konfigur ationsarten @ 0\mod_114052121 0140_3101.doc @ 3196
7.1 Configurations
Pos: 19.3 /Konfigur ation, Parametrierung/ Temperatur/TTR200/Ko nfigurationsar ten TTR200 / HART- Kommunikatio n @ 15\mod_11955733 82203_3101.doc @ 141935
Transmitters can be configured as follows:
via HART protocol and handheld terminal
via HART protocol with FSK modem, PC and Smart Vision configuration software
via DTM in FDT 1.2 network applications
Configuration via field bus (PROFIBUS), if the superordinate I/O system is HART-enabled
(e.g., ABB S800 or S900)
A00212
HART
2
1
3
FSK
Modem
R = 250 Ohm*
b
TTR200
* if necessary
Fig. 12
1 DHH691 (691HT), STT04, HC275, FC375
2 FDT/DTM technology
3 Power supply (process interface)
7.1.1 HART communication
Communication with the transmitter is supported by the HART protocol. The communication
signal is modulated onto both wires of the signal line according to the HART FSK “Physical
Layer” specification, version 8.1 (08/1999). The electrical connection is provided either by two
test pins at the (+) and (–) terminals of the transmitter or by the power supply cable that is
installed on-site. The advantage is that power supplies that are part of the industrial plant allow
remote configuration.