EasyManua.ls Logo

ABB TZIDC - FM Approvals

ABB TZIDC
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ex relevant specifications
42/18-84-EN TZIDC, TZIDC-110, TZIDC-120 65
10.2.5 FM Approvals
TZIDC-110 Positioner, Model V18346-a032b2cd0e
IS/I,II,III/1/ABCDEFG/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C-901265 Entity, FISCO
Entity and FISCO Parameters
Parameters Terminals Type Groups
Vmax Imax Pi Ci Li
+11 / -12 Entity A-G 24 V 250 mA 1.2 W 2.8 nF 7.2 uH
+11 / -12 FISCO A-G 17.5 V 360 mA 2.52 W 2.8 nF 7.2 uH
+11 / -12 FISCO C-G 17.5 V 380 mA 5.32 W 2.8 nF 7.2 uH
+51 / -52 Entity A-G 16 V 20 mA - 60 nF 100 uH
+41 / -42 Entity A-G 16 V 20 mA - 60 nF 100 uH
+85 / -86 Entity A-G 30 V - - 3.7 nF < 1 uH
NI/I/2/ABCD/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
S/II,III/2/EFG//T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
Enclosure type 4x
a = Case/mounting – 1, 2, 5 or 6
b = Output/safe protection – 1, 2, 4 or 5
c = Option modules (shutdown) – 0 or 4
d = Optional mechanical kit for digital position feedback – 0, 1 or 3
e = Design (varnish/coding) – 1 or E
Equipment Ratings:
TZIDC-110
Intrinsically safe, Entity and FISCO, for Class I, II and III, Division 1,
Applicable Groups A, B, C, D, E, F, G; nonincendive for Class I, Division 2,
Group E, F and G hazardous (classified) indoor and outdoort NEMA 4x locations.
The following temperature code ratings were assigned for the equipment and protection
methods described above:
T6 in ambient temperatures of 40 °C
T5 in ambient temperatures of 55 °C
T4 in ambient temperatures of 85 °C