80 | XSE RI ES G5 | 210602 6MNAA
Figure 9-2: S1 Security switch
Legend S1 Security switch
1
Battery
2
Security switch
Ensure the security switch is set to OFF.
On the Station Setup tab, verify that the Security Switch Status field shows Off.
Figure 9-3: Station Setup tab Security switch status
Type a four-digit security code for Security Code Level 1 (read only access).
Type a four-digit security code for Security Code Level 2 (read and write access).
IMPORTANT NOTE: Record the security codes. Once saved, they are not visible on the Station
Setup tab.
Click Send.
On the board, set the XFC
G5
or XRC
G5
security switch to ON.