Error resolution and maintenance – Taking the Wallbox eMH1 out of operation |
23
Proceed as follows to test the RCCB:
1 Open the housing cover of the wallbox using the
key supplied and flip it up.
y For the Wallbox eMH1 Basic, the RCCB is
located in the domestic power distribution:
open the domestic power distribution box.
2 Locate and press the push button engraved T or
marked Test.
y The RCCB should now trip and flick the pivot
lever of the RCCB into a centre position (con-
nection to the power supply is interrupted).
3 Now flip the pivot lever first to the 0 position and
then back to the I position.
4 Close the housing cover of the wallbox and/or the
domestic power distribution box.
Should the RCCB malfunction during testing, you must not continue to operate the wallbox under any
circumstances! Contact a qualified specialist electrical contractor to have the error resolved.
Taking the Wallbox eMH1 out of operation
In case of severe malfunctions or damage to the device, you must take the Wallbox eMH1 out of operation.
To do so, proceed as follows:
1 Open the housing cover of the wallbox (all model
variants except eMH1 Basic) using the key sup-
plied.
2 Flick the pivot lever of the internal RCCB into the
0 position (connection to the electricity grid is
interrupted).