grounding notes
Power to the CSC400 may have
been interrupted
Verify the CSC400 has power locally.
4
Modbus communication
works for writing Remote
Stop, Remote Start, but no
values are being read back
CSC400’s ignition module may
be “sparking”.
The CSC400 will not respond to Modbus requests
when the ignition module is powering its high-voltage
sparker to ignite the Pilot.
If a USB-to-RS485 conversion
cable has been used, the PC test
software may have lost
connection to the virtual COM
port, or noise may have interfered
with USB communications.
Unplug the USB-to-RS485 conversion cable from the
USB port on the PC, wait 10 seconds, then plug it
back in. Retry connecting to the COM port in the test
software.