Parameter Description
C220/C420G General Flux Vector Control Inverter User Manual
95
F5-10
DI filter time
Factory default value
10ms
Setup range
0ms
~
100ms
It is used to set the sensitivity of DI terminal. If the digital input terminal is
vulnerable to interference and may cause error action, it can increase this parameter
value to enhance the anti-interference capability. However, this operation will
reduce the sensitivity of DI terminal.
F5-11
Terminal
command mode
Factory default value 0
Setup
range
0
Two-line mode 1
1
Two-line mode 2
2
Three-line mode 1
3
Three-line mode 2
This parameter defines four different modes of controlling the operation of the
inverter via the external terminals.
0: Two-line running mode 1: This mode is the most commonly used two-line mode.
The forward/reverse rotation of the motor is decided by the commands of FWD and