Planning Your Application Program
Chapter 6
$AAXR
Description Get WDT timeout value
Syntax $AAXR(cr)
dddd is the WDT timeout value in
engineering units. (seconds)
Response Success: !AA(cr)
Fail: ?AA(cr)
Example Command: $01XR
Response: !011234
$AAXEWmm
Description Set WDT timeout slot enable mask
Syntax $AAXEWmm(cr)
mm indicates a 2-character
hexadecimal value representing the
WDT timeout slot enable mask of
the ADAM-5000.
Response Success: !AA(cr)
Fail: ?AA(cr)
Example Command: $01XEWFF
Response: !01