6-4-4 Analog Output Command Set
Command Syntax Command Name Description
$aaSiCjArrff Configuration
$aaSiCjB
Configuration
Status
#aaSiCj(data)Analog Data Out
"Start-Up Output
"Sets the output range, data format
and slew rate for a specified channel in
a specified analog output module in a
specified system."
"Returns the configuration parameters
of a specified channel in a specified
analog output module of a specified
system."
"Sends a digital value from the host
computer to a specified channel of a
specified slot in a specified ADAM-
5000 system for output as an analog
signal."
"Stores a default output value in a
$aaSiCj4
Current/Voltage
Configuration"
specified channel. The output value will
take effect upon startup or reset."
"Directs the specified channel to store
$aaSiCj0 4 mA Calibration
$aaSiCj1 20 mA Calibration
parameters followi ng a calibration for
4 mA output"
"Directs the specified channel to store
parameters followi ng a calibration for
20 mA output"
$aaSiCj3hh Tr i m Calibration
"Trims the specified channel a
specified number of units up or down"
"Returns either the last value sent to
$aaSiCj6
Last Value
Readback
the specified channel by a
#aaSiCj(data) command, or start-up
output current/voltage."
Table 6-9: Analog Output command Set Table