Planning Your Application Program
Analog Input Alarm Command Set
Chapter 6
Command Syntax Command Name Description
$aaSiCjAhs Set Alarm Mode
Sets the High/Low alarm in either
Momentary or Latching mode
$aaSiCjAh Read Alarm Mode
Returns the alarm mode for
the specified channel.
$aaSiCjAhEs
Enable/Disable
Alarm
Enables or Disables the High/Low
alarm of the specified channel
$aaSiCjCh Clear Latch Alarm Resets a latched alarm
$aaSiCjAhCSkCn
Set Alarm
Connection
$aaSiCjRhC
Read Alarm
Connection
Connects the High/Low alarm of a
specified input channel to a specified
digital output channel
Returns the alarm limit output
connection of a specified input channel
$aaSiCjAhU(data)Set Alarm Limit
Sets the High/Low alarm limit
value for the specified input channel
$aaSiCjRhU Read Alarm Limit
Returns the High/Low alarm limit value
for the specified input channel
$aaSiCjS
Read Alarm
Status
Reads whether an alarm occurred for
a specified input channel
Table 6-7 Analog Input alarm command set table
Note: This command set applies to the ADAM-5013, ADAM-
5017, ADAM-5017H/5017UH and the ADAM-5018 .