Appendix B
Data Formats and I/O Ranges
B.2 Analog Input Ranges - ADAM-5017
Module
Range
Code
Input
Range
Description
Data
Formats
+F.S. Zero -F.S.
Displayed
Resolution
Actual
Value
Engineering
Units
+10.000 ±00.000
-
10.000
1 mV
% of FSR +100.00 ±000.00
-
100.00
0.01%
08h ±10 V
Two's
Complement
7FFF 0000 8000 1 LSB
Reading/
1000
Engineering
Units
+5.0000 ±0.0000
-
5.0000
100.00 µV
% of FSR +100.00 ±000.00
-
100.00
0.01%
09h ±5 V
Two's
Complement
7FFF 0000 8000 1 LSB
Reading/
1000
Engineering
Units
+1.0000 ±0.0000
-
1.0000
100.00 µV
% of FSR +100.00 ±000.00
-
100.00
0.01%
0Ah ±1 V
Two's
Complement
7FFF 0000 8000 1 LSB
Reading/
10000
Engineering
Units
+500.00 ±000.00
-
500.00
10 µV
% of FSR +100.00 ±000.00
-
100.00
0.01%
0Bh ±500 mV
Two's
Complement
7FFF 0000 8000 1 LSB
Reading/
10
Engineering
Units
+150.00 ±000.00
-
150.00
10 µV
% of FSR +100.00 ±000.00
-
100.00
0.01%
0Ch ±150 mV
Two's
Complement
7FFF 0000 8000 1 LSB
Reading/
100
Engineering
Units
+20.000 ±00.000
-
20.000
1 µV
% of FSR +100.00 ±000.00
-
100.00
0.01%
ADAM-
5017
0Dh ±20 mA
Two's
Complement
7FFF 0000 8000 1 LSB
Reading/
1000
4
ADAM-
5000/TCP
User’s
Manual