51 WISE-4610(P) User Manual
Appendix A Modbus Table with WISE-4610
Table A.5: WISE-4610-S615 (for WISE-6610 LoRaWAN GW)
RTD (AI) 4 DI - DO -
Address 0X Ch Description Attribute Address 4X Ch Description Attribute
00101 0
Reset Histor-
ical Max. AI
Value
Write 40001 0
AI Value
Read
00102 1 Write 40002 1 Read
00103 2 Write 40003 2 Read
00104 3 Write 40004 3 Read
00105
Average
Ch 0~3
Write
40005
Average
Ch 0~3
Read
00111 0
Reset Histor-
ical Min. AI
Value
Write 40101~40102 0
*AI Status
Read
00112 1 Write 40103~40104 1 Read
00113 2 Write 40105~40106 2 Read
00114 3 Write 40107~40108 3 Read
00115
Average
Ch 0~3
Write
00131 0
AI High
Alarm Flag
R/W 40111 0
Historical
Max. AI Value
Read
00132 1 R/W 40112 1 Read
00133 2 R/W 40113 2 Read
00134 3 R/W 40114 3 Read
00135
Average
Ch 0~3
R/W
40115
Average
Ch 0~3
Read
00141 0
AI Low
Alarm Flag
R/W 40121 0
Historical
Min. AI Value
Read
00142 1 R/W 40122 1 Read
00143 2 R/W 40123 2 Read
00144 3 R/W 40124 3 Read
00145
Average
Ch 0~3
R/W
40125
Average
Ch 0~3
Read
40201 0
Type Code
(The type
codes of
channels for
average
value can't be
changed.)
Read
40202 1 Read
40203 2 Read
40204 3 Read
40205
Average
Ch 0~3
Read
Miscellaneous
Address 0X Ch Description Attribute Address 4X Ch Description Attribute
5001
RTC Battery
Low Event
Read
45004
Battery Level
(0 ~ 100%)