5.4.2 Disconnecting cables between PDU and UPS
1. Unlock the clips and push out PDU from rack cabinet, then rotate the
PDU as below.
2. Disconnect UPS Input / Output cables and RJ11 cable as well as other
cables connected on UPS.
3. Remove out the UPS for service or replacement.
Note: Don’t let the PDU suffer any strong stress during its rotation
position.
5.4.3 Switching PDU to NORMAL mode
1. Check if the input/output/RJ11 cables are connected well, and then
Switch on the PDU input switch, the ups will turn to bypass mode.
2. Rotate the maintenance switch to normal position, screw the
maintenance switch cover to PDU.
3. Press on button on ups LCD panel, the ups will turn to line mode.