To start the UPS on battery:
Check all the connection is correct.
Pressing button continuously for more than 100ms, the UPS would be
powered on. At this time the fan begins to rotate. Then LCD will show the
default UPS status summary screen.
Pressing button continuously for more than 1 second, the buzzer will
beep for 300ms, UPS starts to turn on.
A few seconds later, the UPS turns into Battery mode. If the utility power
comes back, the UPS will transfer to Line mode without output
interruption of the UPS.
6.6.3 UPS shutdown with utility
To shut down the UPS with utility:
Pressing button continuously for more than 3 seconds and the buzzer
will beep 300ms. After that, the UPS will turn into Bypass mode at once.
When completing the above action, UPS output voltage is still present. In
order to cut off the UPS output, simply cut off the utility power supply. A
few seconds later, the ups will shut down and no output voltage is
available from the UPS output terminal.
6.6.4 UPS shutdown without utility
To shut down the UPS without utility:
To power off the UPS by pressing button continuously for more than 3
second, and the buzzer will beep for 300ms. The UPS will cut off the
output at once.
A few seconds later, the ups will shut down and no voltage is available
from the UPS output.