To check the Event log:
1. By pressing on the menu of “Event log”.
2. Scroll through the listed events or faults.
3. The following table describes typical conditions.
Conditions
Possible cause
Action
Battery mode
Battery (Orange) LED
is On.
1 beep every 4
seconds.
Code: 168
A utility failure has
occurred, and the
UPS is in Battery
mode.
The UPS is powering
the equipment with
battery power.
Prepare your
equipment for
shutdown.
Battery low
Battery (Orange) LED
is On.
1 beep every 1
second.
Code: 56
The UPS is in Battery
mode and the battery
is running low.
This warning is
approximate, and the
actual time to
shutdown may vary
significantly.
Depending on the
UPS load and number
of Extended Battery
Modules (EXTERNAL
BATTERY MODULE s),
the "Battery Low"
warning may occur
before the batteries
reach 20% capacity.
No battery
Fault (Red) LED is
Flash
1beep every 1 second
Code: 199
The batteries are
disconnected.
Verify that all
batteries are properly
connected.
If the condition
persists, contact your
service
representative.
8.
TROUBLESHOOTING