67
Line input different
Fault (Red) LED is
flash
1 beep every 1
second
Code: 132
Parallel system
UPS1 line okUPS2
line loss
Check the line input
Power strategy
different
Fault (Red) LED is
flash
1 beep every 1
second
Code: 135
In parallel system
UPS mode
(normal, converter,
HE) is different
Check UPS
operating
mode and keep
operating mode the
same on all systems
Rate power different
Fault (Red) LED is
flash
1 beep every 1
second
Code: 137
Parallel system rate
power different
Rated power is
different, not allowed
to turn on UPS.
Keep rated power the
same on all systems
HE in parallel
Fault (Red) LED is
flash
1 beep every 1
second
Code: 136
Parallel system
UPS
mode set as HE
HE not allowed in
parallel system
change UPS mode
8.1 Silencing the alarm
Press the button for 3s on the front panel display to silence the
alarm. Check the alarm condition and perform the applicable action to
resolve the condition.
If the alarm status changes or press the button 3s on the front
panel display, the alarm beeps again, overriding the previous alarm
silencing.