6.7.5 The control menu
By pressing on the menu of “Control”, the display would enter the
next control menu tree.
Start Battery Test: this is one command that control the UPS to do the
battery test.
Reset Fault status: when fault occurs, UPS would keep in Fault mode and
alarm. To recover to normal status, enter this menu to reset error status,
then UPS would stop alarm and recover to bypass mode. And the reason
of fault should be checked and deleted before UPS is turned on again by
manual operation.
Restore factory settings: all the settings would be recovered to default
factory settings. It could only be done in Bypass mode.
UPS Status
Event Log
Measurements
Control
Identification
Settings
Menu
02/ 28/2019 13: 01
Event #58
Output Short Circuit
3/3
2/3
15:
44
02/ 28/ 2019
Event #1999
Clock set done
1/3
09: 05
03/ 01/ 2019
Alarm #25:
Output Overload