EasyManua.ls Logo

AEG Protect D Series - Page 48

AEG Protect D Series
82 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48
Load alarm
level
[10%], [20%], [30%], …, [100%]
100%
Reserved
(unused)
Power
strategy
[High performance mode(normal)],
[Economical
mode(ECO)],[converter],[High
efficiency mode(ECO+)]
High
performance
mode(normal)
Start w/o
mains
[enabled], [disabled]
e
nabled
Battery
saving mode
[disabled], [10%], [20%], …, [100%]
d
isabled
Site wiring
fau
lt alarm
[enabled], [disabled]
disable
Battery
charge % to
restart
[0
%
], [10
%
], [20
%
], …, [100
%
]
0
Automatic
battery
support tests
[enabled], [disabled],
enabled
Periodic
battery test
[daily], [weekly], [monthly]
weekly
Ambient
temperature
high
alarm
[enable], [disable]
Enable(40
o
C)
REPO
operation
[normally open], [normally closed]
Normally
closed
Reset
Cumulative
Consumption
kWh
When “
y
es” is selected the
Cumulative Consumption kWh value
is cleared and the Date & Time stamp
for this statistic is set to the current
date & time.
n
o”
Battery limit
time
disable,1h,2h,....,14h,15h,16h,…999h,
14h
Auto reboot
[enable], [disable]
enable
Auto
bypass
[enabled], [disabled]
enable
Start without
battery
[enable], [disable]
disable
Clear event
log
-
display
present
number of
events
LCD contrast
-
5,
-
4,
-
3,
-
2,
-
1, 0 ,+1,+2,+3,+4,+5
0

Table of Contents