106
In Detail
Device application conditions
Built-in device (VDE0160) EN 50 178
General requirements EN 60146-1-1
Design, vertical installation
Operating conditions EN 60 146-1-1; ch. 2.5
Area of application, industrial CISPR 6
Temperature behaviour EN 60 146-1-1; ch. 2.2
Storage temperature D -25°C - +55°C
Transport temperature E -25°C - +70°C
Operating temperature better B -10°C - +35°C
with forced ventilation
-10°C - +45°C with natural air cooling
-10°C - +55°C
with reduced type current -2%/°C
Use of the device in UL conditions
up to a maximum ambient
temperature of 40°C.
Load category 1 EN 60 146-1-1 P.2
Humidity class B EN 50 178 Tab. 7 (EN 60 721)
Overvoltage category III EN 50 178 Tab. 3 (849V)
Degree of contamination 2 EN 50 178 Tab. 2
Air pressure 900 mbar*; 1000 m above sea level
Degree of protection IP00 EN 69 529
Protection class I EN 50178 chap. 3
Air and creepage distances housing / mains potential > 5.5 mm
housing / control pot. > 1 mm
mains volt. / control pot. > 10 mm
mains volt. among each other
2.5 mm
Mechanical shocks EN 50 178 chap. 6.2.1
Test voltage EN 50 178 tab. 18
Tests in acc. with EN 60 146-1-1 4.
EMC emitted interference EN 61000-6-4
Radio interference suppression
Control unit Class A EN 55011; CISPR 11
EMC interference immunity EN 61000-6-2
Compatibility level Class 3 EN 61000-2-4
ESD 8 kV (A) EN 61000-4-2
Electromagnetic fields 10 V/m
EN 61000-4-3