Modulex E8 Controller and BCM
Operations and Maintenance Manual
Table 8-2: USER Menu Sub-Menus and Parameters (Continued)
HTG CIRCUIT 1 Sub-Menu
MODE Displays Timer Mode for Boiler
- - - -, Standby,
Auto 1, Auto 2,
- - - -
T-ROOM DES 1
Room temperature setting for first
41.0°F – 104.0°F 68.0° F
T-ROOM DES 2
Room temperature setting for second
41.0°F – 104.0°F 68.0° F
T-ROOM DES 3
Room temperature setting for third
41.0°F – 104.0°F 68.0° F
T-REDUCED
Reduced night-time room temperature
41.0°F – 104.0°F 50.0° F
T-ABSENCE
Required room temperatures during
41.0°F – 104.0°F 59.0° F
T-LIMIT DAY Applies during day-time heating periods
- - - -,
66.0°F
T-LIMIT N
Applies during reduced night-time
- - - -,
50.0°F
HEATSLOPE
Indicate number of degrees that that the
flow temperature changes if the outside
temperature increases or decreases by 1°F.
0.00 – 3.00 1.20
MAX OPT-TIME
Only active if OPTIM HEAT is set to 01 or
0:00 – 3:00 [h] 2:00 [h]
PC-ENABLE
Code Number for enabling access to
heating circuit data from a Personal
0000 – 9999 0000
RETURN
Press Program Key to exit HTG CIRCUIT 1
HTG CIRCUIT 2 Sub-Menu
Functions for HTG Circuit 2 are identical to HTG Circuit 1 Functions listed above.
SOLAR M / F Sub-Menu (No Functions Currently In This Sub-Menu)
RETURN
Pressing the Program Key with SOLAR M/F
displayed will change display to RETURN.
Press Program Key again to redisplay
SOLAR M/F. Turning the Rotary Knob
clockwise will advance thd display to the
N/A