Modulex E8 Controller and BCM
Operations and Maintenance Manual
8.2 USER Menu
The USER Menu contains exactly the same sub-menus as the DISPLAY Menu. However, the
USER Menu items are not “Read Only” and therefore can be changed if desired.
Table 8-2: USER Menu Sub-Menus and Parameters
FUNCTION
DESCRIPTION
ENTRY RANGE
DEFAULT
INSTALLATION Sub-Menu
LANGUAGE Selects display language.
12 languages
are available.
ENGLISH
CONTRAST Adjusts display contrast
-20 to 20
00
DISPLAY SEL
Sets the day of the week or the sensor
temperature (°F) to appear in the display
when the swing-down panel is closed.
Day: SUN – SAT
T-OUTSIDE: Outside Temperature
FLOW TEMP (1/2): Flow Temp. For
supply water
temperature. (Only if
sensor is installed)
T-DHW: Domestic Hot Water
Temp
T-BOILER; Heat Generator Temp.
T-ROOM (1 / 2): Room Temp, Heating
Circuit 1 or 2 (ONLY if
Remote Control is
See
DESCRIPTION
Column
- - - -
RETURN
Press Program Key to exit INSTALLATION
HOT WATER Sub-Menu
Enables storage tank for heating
T-DHW 1, 2 or
Hot Water set point for enable time 1, 2,
50°F – 158°F 140°F
CIRCL-P-DHW
Circulation Pump for Domestic Hot
00, 01 (OFF/ON) 00 = OFF
RETURN
Press Program Key exit HOT WATER