EasyManuals Logo

Aerco MODULEX EXT 321 User Manual

Aerco MODULEX EXT 321
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS
Installation, Operation & Maintenance Manual
Page 12 of 146 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0087_0F
07/13/15 Phone: 800-526-0288 GF-143
WARNING!
Should overheating occur, or the gas supply fail to shut off, do not
turn off or disconnect the electrical supply to the pump. Instead,
shut off the gas supply at a location external to the boiler.
Water Quality Requirements 1.8.3
NOTE
For additional information concerning water quality and treatment,
refer to AERCO technical documents Glycol Directive and AERCO
Piping Application Guide (GF-136-P).
Unsuitable heating system water can cause the formation of scale or sludge, which affects system
efficiency. It can also cause corrosion and reduce life of the heat exchanger.
You must follow guidelines for boiler water quality.
Thoroughly flush the system prior to filling.
Follow the cleaning instructions.
Never use water to fill the heating system that has been treated by reverse osmosis,
deionization, or distilled water in order to soften the water.
Do not use inhibitors or other additives unless approved by AERCO for that purpose.
When frost protection of the heating system is desired, only use AERCO-approved
antifreezes. The allowed maximum concentration is 50%.
When using oxygen-permeable pipes, e. g. for under floor heating systems, you must
separate the system from the boiler using plate heat exchangers.
Close the valves of the boiler while flushing the system, do not introduce any system cleaner
into the boiler loop. Flush system thoroughly to remove all system cleaner before filling boiler.
Approved antifreeze (maximum concentration of 50%):
Rhomar RhoGard Mutli-Metal (AL safe)
Noble Noburst AL
Approved system cleaners:
Noble Noburst Hydronic System Cleaner
Fernox F3 Cleaner
Rhomar Hydro-Solv 9100
The system cleaners from NoBurst, Rhomar, and Fernox are NOT to be used in the boiler itself.
The boiler must be closed off (valves closed) from the rest of the system or not connected while
the cleaners are in the system. The system should then be drained and then thoroughly flushed
with clean water to remove all the system cleaner.
Approved inhibitors:
Rhomar Pro-tek 922
Noble Noburst AL inhibitor
AERCO/Sentinel products. See list in GF-136-P, section 2.3 - System Flushing,
Treatment, and Cleansing.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aerco MODULEX EXT 321 and is the answer not in the manual?

Aerco MODULEX EXT 321 Specifications

General IconGeneral
BrandAerco
ModelMODULEX EXT 321
CategoryBoiler
LanguageEnglish

Related product manuals