No electric voltage
Check the presence of voltage
Check the safety systems upstream from the
appliance
Master switch at OFF

Control panel at OFF
Main switch at OFF
Compressor magnet circuit breaker at OFF
Position at ON
Power supply voltage too low Check power supply line
Remote control switch coil broken
Circuit board broken
Peak condenser broken
Compressor broken
Replace the component

No refrigerant
Appliance dimensioning
Functioning outside of operational limits
Check

Liquid return to the compressor
Inadequate fixing
Check
 Invert a phase

Contacts between metal bodies Check
Weak rest Restore
Loose screws Tighten the screws


Excessive flow pressure
Low intake pressure
Power supply voltage low
Electric connections fastened badly
Functioning outside of operational limits
Check
Pressure switch functions badly Replace the component
Circuit breaker protection intervention
Check power supply voltage
Check electric isolation of the windings

High external air temperature
High water input temperature
Check
Insufficient air flow
Insufficient water flow
Check fan functioning
Check pump functioning
Fan regulation anomalous functioning Check
Air in the hydraulic system Bleed
Excessive gas load Check

Low external air temperature
Low water input temperature
Check
Humidity in the cooling circuit Empty and restore the gas load
Anomalous functioning of fan regulation (if

Check
Air in the hydraulic system Bleed
Insufficient gas load Check

High external air temperature
High water input temperature
Thermostatic expansion valve too open or dam
-
aged
Check

Low external air temperature
Low water input temperature
Thermostatic expansion valve damaged or blocked
Water filter blocked
Plate heat exchanger blocked
Check
Insufficient air flow
Insufficient water flow
Check fan functioning
Check pump functioning
