18
Pressure drops
A = Ø 1”
B = Ø 1”1/4
C = Ø 1”1/2
The pressure drops in the charts above
refer to an average water temperature
of 10 °C. The following table shows the
corrections to apply to the pressure drops
with a variation in average water tempe-
rature.
0
20
40
60
80
100
120
024681012
A
B
C
D
E
F
G
H
I
L
Water flow (m
3
/h)
Pressure drop (kPa)
Evaporator pressure drops
0
20
40
024681012
A
B
C
Water flow (m
3
/h)
Pressure drop (kPa)
Water filter pressure drops
A = ANZ 0207
B = ANZ 0257
C = ANZ 0307
D = ANZ 0417
E = ANZ 0507
F = ANZ 0807
G = ANZ 0907
H = ANZ 1007
I = ANZ 1507
L = ANZ 2007
Model
0207 0257 0307 0417 0507 0807 0907 1007 1507 2007
Water filter 1”

Water filter
1”1/4

Water filter
1”1/2

Average water temperature (°C)
5101520304050
Correction factor 1,020 1,000 0,985 0,970 0,950 0,930 0,910

Related product manuals