5.3 H VERSIONS TECHNICAL DATA
COOLING 015H 020H 025H 030H
Cooling capacity kW 5,3 6,9 8,2 9,7
Total absorbed power kW 1,7 2,0 2,3 2,7
Evaporator water flow rate l/h 910 1.190 1.410 1.670
Condenser water flow rate l/h 1.190 1.500 1.780 2.100
Condenser pressure drop kPa 6,3 6,2 6,1 6,3
Condenser water consumption at 16 °C (1) l/h 320 400 470 560
Condenser water pressure drop at 16 °C kPa 1,0 1,5 1,2 1,6
HEATING
Heating capacity kW 6,1 7,8 9,3 10,9
Total absorbed power kW 2,2 2,7 3,2 3,7
Condenser water flow rate l/h 1.050 1.340 1.600 1.880
Water consumption at the evaporator at 10 °C (1) l/h 690 900 1.080 1.270
Evaporator pressure drop at 10 °C kPa 2,0 2,2 2,2 2,3
ENERGY INDEXES
EER
W/W
3,12 3,45 3,57 3,59
COP
W/W
2,80 2,88 2,92 2,94
ESEER
W/W
3,78 4,25 4,45 4,42
ELECTRICAL DATA
Power supply A 230V
~
- 50 Hz
Absorbed current COLD A 8,6 9,4 11,1 13,0
Absorbed current HOT A 10,5 12,6 14,9 17,5
Maximum current A 13 15 18 24
Peak current A 48 61 76 100
COMPRESSORS (SCROLL)
Number per circuit/type n°/n° 1/Rotary 1/Scroll 1/Scroll 1/Scroll
EVAPORATOR (PLATES)
Number 1 1 1 1
Hydraulic connections ø gas M 1" 1" 1" 1"
CONDENSER (PLATES)
Number 1 1 1 1
Hydraulic connections ø gas M 1" 1" 1" 1"
STORAGE
Water storage l 23 23 23 23
PUMP
Absorbed power kW 0,095 0,165 0,18 0,2
Absorbed current A 0,42 0,8 0,8 0,8
Effective pressure to the plant kPa 54 63 61 59
SOUND DATA
Sound power level dB(A) 56,0 56,5 57,0 57,5
Sound pressure dB(A) 47,5 48,0 48,5 49,0
DIMENSIONS
Height mm 625 625 625 625
Width mm 404 404 404 404
Depth mm 504 504 504 504
EMPTY weight
kg 87 98 100 103
In cooling mode
- Outlet water temperature 7 °C
- Water inlet temperature to condenser 30 °C
- t 5°C
In heating mode
- Outlet water temperature 50 °C
- Water inlet temperature to
evaporator 10 °C
- t 5°C
- Sound pressure measured in 85 m
3
semi-
reverberant test chamber with reverberation
time Tr = 0.5 sec.
NOTE
(1) The consumption of water at 16 °C refers
to a unit with pressure switch valve, which is
appropriately calibrated.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC VENICE Series and is the answer not in the manual?

AERMEC VENICE Series Specifications

General IconGeneral
BrandAERMEC
ModelVENICE Series
CategoryHeat Pump
LanguageEnglish

Related product manuals