54
12. Installation checks
LPG system
Always check the LPG gas system for leaks according to the relevant regulations after installation
or service.
• If a leak is suspected, locate it using leak detector spray or soapy water.
• Check that the reduction valve is set to the right pressure (30 mbar).
The heating system
•
•
Checks can be performed in two ways. Either by leak detection at 0.75-1.0 bar over 15 min.,
• Check the glycol mix in the expansion tank. The level must be approx. 1 cm above the MIN. line
(Fig. 23) when the system is cold. Make sure the system is properly vented before running it.
• Check that the circulation pump rpm are correctly set; see section 7. Installing pumps
in the expansion tank sloshes around and it sounds as if pump rpm are set too high, reduce circula-
tion pump rpm.
• Check that the boiler can be started on gas and electricity.
• Ensure full heat comfort and circulation in the system.
The water system
• Check the fresh water system and the boiler for leaks. Carefully check that all connections between
the boiler and water system are properly sealed.
Other
Check that:
• The vent and drain hoses on the expansion tank are not clogged.
• Draining from the fresh water system works (see section 5.11 Connection to fresh water system).
•
• Serial number and installation date are shown in the boiler service record.
•
•
•
10 °C in order for AC to begin
cooling, or exceed 4 °C to begin heating.
• -
terborne heating, air must be able to pass freely through air gaps under the bed boxes, behind the
air supply to the convectors. It is also important that curtains, cushions and blankets do not prevent
air circulation behind seatback cushions.
Fire/explosion risk
WARNING