Rockwell Automation Publication 1734-UM013C-EN-P - August 2010 117
Considerations When Replacing POINT Guard I/O Modules Chapter 8
If the configuration downloaded to the module was not from the original
DNT file, the configuration signature will not match the original. Even if
you recreate the same parameters in a new DNT file, the time and date
portions of the signature will be different so the connection to the
SmartGuard controller is not made. If this occurs, click the Safety
Connection tab for the SmartGuard controller that prompts you that the
signature is different and provides you with the option to match the new
signature. However, you should first re-validate the safety system, because
it is not using the original DNT file.
7. Click Yes.
This takes the SmartGuard controller our of Run mode.
You se e this dialog box.
8. Click Yes to download the new connection configuration to the
SmartGuard controller.
After the download is complete, place the SmartGuard controller back in
Run mode and the connection to the replacement module is established.
9. Follow your company-prescribed procedures to functionally test the
replaced I/O module and system and to authorize the system for use.