114 Rockwell Automation Publication 1734-UM013C-EN-P - August 2010
Chapter 8 Considerations When Replacing POINT Guard I/O Modules
GuardLogix Controllers versus SmartGuard Controllers
There is one major difference in functionality between the GuardLogix and
SmartGuard safety controllers that affects the replacement of safety I/O modules.
GuardLogix controllers retain I/O module configuration on-board and are able
to download the configuration to the replacement module. SmartGuard
controllers do not retain I/O module configuration so you need to use
RSNetWorx for DeviceNet software to download the configuration to the
replacement module.
Replacing an I/O Module
When Using a SmartGuard
Controller
Follow these steps to replace an I/O module when using a SmartGuard controller.
1. Replace the module and match the node number of the original module.
2. In RSNetWorx for DeviceNet software, open your project.
If the replacement module is out-of-box or has an SNN that does not
match the original module, the module appears with an exclamation mark.