Rockwell Automation Publication 1734-UM013C-EN-P - August 2010 75
Configure the Module in a GuardLogix Controller Chapter 6
12. From the Input Data pull-down menu, choose the appropriate method for
the input module, Safety or None.
13. From the Output Data pull-down menu, choose the appropriate method
from the following options.
Choose Description
Safety These tags are created for the target module:
• RunMode for module mode
• ConnectionFaulted for communication status
• Safety Data for safety inputs from the module
The test outputs that are configured as standard outputs
on the module must not be used for safety purposes.
Choose Description
None Results in an input only connection to the module. Inputs
and status are read, but no outputs are written. You can
still use the test outputs as pulse test outputs or a power
supply.
Test
(1)
Creates these tags to enable network control of the test
outputs on the module. This selection allows the test
outputs to be used as standard outputs and muting
outputs.
(1) To have this choice from the pull-down menu, you must choose ‘This Controller’ from the Configured
By pull-down menu.